Objectives:
This procedure checks that the instrument is still in good operational condition post landing. It will also get a background measurement at the end.
Block Name: tega_checkout.vml
Version #: R30
Configuration: Landed Operations: Surface Phase Characterization
Assumptions: TEGA can not be turned on below -50C
Gas(es) used: Calibration and Carrier Gas Tanks still sealed. Manifold will be pressurized with Mars ATM during valve checkout.
Filaments used: 0
SW Version (386): V513 SW Version (EGA): V321
Sweep and hop mode version(s): V112
Super modes and Sweep modes used: SM 1 & SM 2, Sweep Modes 37 & 38
Sequences used: 1B (& 2B), 3B (& 4B), 1A, 32A(&33A), 34A(&35A)
-
1) Turn TEGA ON (tega_power_on)
-
a) Add preheat pause as pass in duration determined by thermal environment
-
2) Turn EGA ON, restoring modes from EEPROM 0 (calls tega_ega_on, Restore modes Side 0)
-
a) EGA Transmit time 5 sec. (done within tega_ega_on)
-
b) Run Sweep Mode 37 dark. (done within tega_ega_on)
-
3) Change model power to Ramp1 for Cal Tank and Manifold Heater
-
4) Start Calibration Heater regulation at 20C
-
5) Start TA Manifold Heater regulation at 20C
-
6) Call tega_ega_prep (Filament 0)
-
a) Jplate 0 = -110V, Jplate 1= -92V
-
b) Filament current low current, low energy (0,0,0)
-
c) Start SM 1
-
d) MV ON @ 2800V
-
e) Ion Pump ON
-
f) Change filament current to low current, high energy (0,0,3)
-
g) Pause 2 minutes
-
h) Stop SM 1
-
-
7) Stop Manifold Heater regulation (~ 3 seconds has elapsed)
-
8) Call tega_ega_calibration_scans, Calibration Set 2
-
a) MV @ 3200V
-
9) Turn Calibration Heater regulation OFF (~ 4 minutes have elapsed)
-
10) Call tega_ega_gain
-
a) Start SM 2
-
b) Pause 1 minute
-
c) Set MV 2600 – 3400V (1 minute per voltage)
-
d) Remain at 3200V
-
e) Stop SM 2
-
f) Run Sweep 38
-
11) Start SM 2
-
12) HEATER TEST
-
a) Plumbing 1 – ON Wait 5 secs
-
b) Plumbing 1 – OFF
-
c) Plumbing 2 – ON Wait 5 secs
-
d) Plumbing 2 – OFF
-
e) EGA Manifold – ON Wait 5 secs
-
f) EGA Manifold – OFF
-
g) EGA Plumbing – ON Wait 5 secs
-
h) EGA Plumbing – OFF
-
i) EGA Warmup – ON Wait 5 secs
-
j) EGA Warmup - OFF
-
k) Transfer Tube – ON Wait 5 secs
-
l) Transfer Tube – OFF
-
m) Wedge Heater – ON Wait 5 secs
-
n) Wedge Heater – OFF
-
13) Call tega_select_oven
-
14) Setup for TA test
-
a) Turn on engineering readings for TA test
-
b) open door time to 10 sec
-
c) close oven time to 10 sec
-
d) LED min diff to -1
-
e) Poke registers to setup oven, shield, and t-heater
-
f) Change power model to Ramp2
-
15) Select Oven 0
-
a) Open Door – 10 secs (This has a 30 sec timeout for GV_TEGA_TA_DONE)
-
b) Open inlet – wait 5 sec
-
c) Close inlet –
-
d) Open Outlet – wait 5 sec
-
e) Close Outlet –
-
f) Start Oven fill – Shake for 15 secs (verifies LED operational)
-
i) Will not shake/LED Diff Parameters set to prevent
-
g) Close Oven – 10 secs (This has a 30 sec timeout for GV_TEGA_TA_DONE)
-
h) Poke registers for oven, shield, t-heater (allow enough time to get a linear temperature rise)
-
i) Turn off power to oven, shield, t-heater for one minute.
-
16) Repeat 23a-23i through Oven 7
-
17) Bypass OPEN – Wait 5 secs
-
18) ass CLOSED –
-
a) Issue FPGA Register Dump
-
19) Carrier Valve OPEN – wait 3 sec
-
a) Issue FPGA Register Dump
-
20) Carrier Valve CLOSE –
-
a) Issue FPGA Register Dump
-
21) Calibration Valve OPEN – wait 3 secs
-
a) Issue FPGA Register Dump
-
22) Calibration Valve CLOSE –
-
a) Issue FPGA Register Dump
-
-
23) FPGA Dump to confirm valve states
-
24) Multiplier Voltage to 2800V
-
25) Pause 1 minute
-
26) Stop SM 2
-
27) Run Sweep 38 (2800) and wait for it to finish
-
28) EGA OFF
-
29) TEGA OFF