October
2, 2008 TEGA_High-Temp_TA7_Day2_v1_r2.doc
TEGA High-Temp Soil (TA7_plugged) DAY 2
Power on and perform Day-2 of a full high-temperature ramp on the sample in TA7, which has been previously heated via
midday-1 High-temperature ramp. This sample had a plugged frit during the low and mid-T runs, and is assumed to be plugged here. The purpose of this run is to
provide a baseline for the enthalpy associated with decomposition of altered minerals found on Day-1 and to provide a baseline for
the gases given off by the decompositions. We are flowing no carrier gas, so the calling block will be identical to the Day-1 block except that the TA Sample valve is left closed throughout the run.
High-temperature Day-1 ramp has been completed previously. The carrier valve is closed and the TA manifold has no gas in it. It was emptied during the Day-1 procedure.
The carrier valve will not be operated due to its erratic behavior. Software updates were made post Sol 113 to the 386SW and the mode table was changed to V125
Inputs:Multiplier Voltage: __3300Calibration Set: 3Ch 4 Calibration Voltage: 2800Pump Nudge needed: Yes Venting Oven #: Will not vent -(none)Pre-heat duration: 30 secsCalibrate Channels: 1,4Oven Close Time: NA Select TA #: 7TA# for Check:
N/AEmission: LowCal Tank Temperature: -99C
Constraints:Gas(es) used: Mars ATM will be collected through the TA Sample valve.
October
2, 2008 TEGA_High-Temp_TA7_Day2_v1_r2.doc
TEGA High-Temp Soil (TA7_plugged) DAY 2
SW Version (386): V515 SW Version (EGA): V321
Sweep and hop mode version(s): MODE TABLE V125.
Supermodes and Sweep modes used: Supermodes 1, 2, 3, 4, 6, and 7; Sweeps 37, and 38.
Note: TEGA is checked to see if TEGA is safed. If so, abort self to end activity
4. Pre-heat delay 30 secs
10.1. (LOW), Calibration Set 3
10.2. Calls tega_ega_prep, filament-1
10.2.1.1. Sets JPlate 0 to -107V
10.2.1.2. Sets Jplate 1 to -92V
10.2.1.3. Pause 5 seconds
10.2.1.4. Set MV 3300 (input variable)
October
TEGA High-Temp Soil (TA7_plugged) DAY 2
10.2.1.5. Ion Pump ON
10.2.1.6. Start SM 1, pause 1 sec
10.2.1.7. Emission ON
10.2.1.8. Pause 2 Minutes
10.2.1.9. Stop SM 1
10.2.1.10. Emission ON
10.2.1.11. Pause 2 Minutes
10.2.1.12. Stop SM 1
10.3. Pause 2 minutes (provides time for ion pump to stabilize)
10.4. Change engineering transmit to 10 secs
10.4.1. IF pass thru = 1, emission current will change to HIGH
10.5. Call tega_ega_calibration_scans
10.5.1. calibration_set _____3________
10.5.2. hi_emission_______LOW ____
10.5.3. cal_channels______1,4______
10.5.4. cal_voltage ______3300V ____
10.5.5. cal_4_voltage_____2800V ____
10.5.6. exit_voltage ______3300V ____
| 10.6. | Wait 1 second |
|
|---|---|---|
| 10.7. | Start SM 3 |
|
| 10.8. | Pause 20 minu | tes |
| 10.9. | Stop SM 3 |
|
| 10.10. | Pause 1 minute |
|
| 10.11. | Calls tega_ega10.11.1.1.1. 10.11.1.1.2. 10.11.1.1.3. 10.11.1.1.4. 10.11.1.1.5. 10.11.1.1.6. | _gain Start SM 2 Pause 1 minute Set MV 2600 – 3400V (1 minute per voltage) Exit at 3300_V (input variable) Stop SM 2 Run Sweep 38 |
EGA is warmed up and ready to go (54 mins)
11. Reinforce Emission on
(IF pump nudge is YES Steps 12 to 14 are followed, if NO skip to 15)
- 3 - October
TEGA High-Temp Soil (TA7_plugged) DAY 2
18. Set
18.1. Manifold Pressure
18.2. Outlet Pressure
18.3. Bus A Current
18.4. Bus B Current
Remember to turn on current monitoring to shut down manifold heater (Do not turn manifold heat back on after turning it off in the ramp.)
Execute Sequence 24 B to increase readings on temperature regulation.
23.1.1. TA Manifold +65C
23.1.2. Plumbing 1 +65C
23.1.3. Plumbing 2 +35C
23.1.4. Transfer Tube +75C
23.1.5. EGA Plumbing +45C
23.1.6. EGA manifold to +35 C
23.1.7. Wedge Heater @ 10% duty cycle
24. Pause for Delay_2 (467 sec;) – TWEAKABLE
October
TEGA High-Temp Soil (TA7_plugged) DAY 2
Measure Atmosphere
.
650 C temperature.
October
TEGA High-Temp Soil (TA7_plugged) DAY 2
44. Start SM 7
49. Pause 1 min (to watch gas drain out of CML)
Shut down
October
TEGA High-Temp Soil (TA7_plugged) DAY 2
62. CLOSE GEC Vent Valve
Formatted: Bullets and Numbering
64.1. Turn off the third TEGA switch
64.2. Turn off the second TEGA switch
64.3. Turn off the first TEGA switch
64.4. FPGA Dump – Aker Valve state
Open TA sample valve (to reduce pressure to ambient in CML volume) Close TA sample valve